Henan Hengyu Electric Group Co., Ltd.






20kV, SC(B) series epoxy resin casting dry-type transformer
Classification:
Key Words:
10kV, 20kV, SC(B) series epoxy resin casting dry-type transformer
Mailbox:

Product Model Meaning
model number | S | C | (B) | - | □ | □ | / | □ |
number meaning | three-phase (physics) | Epoxy resin casting type | Foil coils are available for low voltage |
| Performance Level Designator | Rated capacity (kVA) |
| Voltage level (kV) |
Product Overview
20kV, SC(B) series dry-type transformers can be used as the upgrading products of oil-immersed distribution transformers, and are the products with the best performance among all kinds of dry-type transformers, especially suitable for urban power grids, high-rise buildings, business centers, theaters, hospitals, hotels, tunnels, subways, stations, docks, airports, underground power stations, laboratories, combined substations and other important places.
Product Features
1.All-copper winding structure: High-voltage/low-voltage are made of copper (copper wire or copper foil), glass fiber reinforced epoxy resin vacuum casting, forming a high-strength cylinder, excellent mechanical properties, low local discharge electrode, excellent reliability.
2.safety and environmental protection: Flame retardant and explosion-proof design, self-extinguishing insulating materials do not produce toxic gases, no risk of environmental pollution, short circuit without arc potential.
3.Strong weather resistance: Coil moisture resistance and corrosion resistance, special anti-corrosion treatment of the iron core, adapting to 100% humidity and harsh environments, intermittent operation without maintenance.
4.High reliability: Excellent performance of short-circuit and lightning impact resistance, to ensure the stability of the power grid.
5.Efficient heat dissipation: Thin resin layer optimizes heat dissipation, standard natural air cooling (AN), optional air cooling system (AF) to enhance overload capacity.
6.Economic and efficient: Low-loss design, energy-saving and maintenance-free operation, low life cycle cost.
7.Compact and flexible: Small size, light weight, installation without oil tank/fire fighting facilities, saving space and infrastructure costs.
8.Nearby deployment: Can be dispersed in the load center, shorten the low-voltage lines, reduce the comprehensive investment.
Product Certificate
Transformer Workshop

20kV, SC(B)10 dry-type transformer | ||||||||||
Rated Capacity | Linkage group labeling | voltage combination | No-load current | Load Losses at Different Insulation Thermal Ratings | No-load loss | Short Circuit Impedance | ||||
High voltage | High-voltage tap range | Low Voltage | B | F | H | |||||
50 | Yyn0 | 20 | ±5 | 0.4 | 2.2 | 1160 | 1230 | 1320 | 340 | 6.0 |
100 | 2.0 | 1880 | 1990 | 2130 | 540 | |||||
160 | 1.6 | 2340 | 2470 | 2660 | 675 | |||||
200 | 1.6 | 2800 | 2940 | 3140 | 740 | |||||
250 | 1.4 | 3260 | 3420 | 3710 | 840 | |||||
315 | 1.4 | 3890 | 4080 | 4370 | 970 | |||||
400 | 1.2 | 4650 | 4840 | 5180 | 1150 | |||||
500 | 1.2 | 5510 | 5790 | 6170 | 1350 | |||||
630 | 1.0 | 6530 | 6840 | 7360 | 1530 | |||||
800 | 1.0 | 7810 | 8260 | 8830 | 1750 | |||||
1000 | 0.8 | 9230 | 9780 | 10450 | 2070 | |||||
1250 | 0.8 | 10920 | 11540 | 12350 | 2380 | |||||
1600 | 0.8 | 13090 | 13870 | 14860 | 2790 | |||||
2000 | 0.6 | 15480 | 16380 | 17570 | 3240 | |||||
2500 | 0.6 | 18380 | 19380 | 20710 | 3870 | |||||
2000 | 0.6 | 16910 | 17860 | 19000 | 3240 | 8.0 | ||||
2500 | 0.6 | 20230 | 21280 | 22700 | 3870 | |||||
Note: The above data is only for reference when designing and selecting, and the final data is subject to the real thing. |
20kV, SC(B)11 dry-type transformer | ||||||||||
Rated Capacity | High voltage | High-voltage tap range | Low Voltage | Linkage group labeling | No-load loss | Load Loss(W) | No-load current | Short Circuit Impedance | ||
B | F | H | ||||||||
50 | 20 | ±2.5 | 0.4 | Dyn11 | 305 | 1160 | 1230 | 1310 | 1.80 | 6 |
100 | 485 | 1870 | 1990 | 2130 | 1.60 | |||||
160 | 600 | 2330 | 2470 | 2640 | 1.40 | |||||
200 | ±2×2.5 | 655 | 2770 | 2940 | 3140 | 1.40 | ||||
250 | 755 | 3220 | 3420 | 3660 | 1.12 | |||||
315 | 870 | 3850 | 4080 | 4360 | 1.20 | |||||
400 | 1030 | 4650 | 4840 | 5180 | 1.00 | |||||
500 | 1210 | 5460 | 5790 | 6190 | 1.00 | |||||
630 | 1370 | 6450 | 6840 | 7320 | 0.90 | |||||
800 | 1570 | 7790 | 8260 | 8840 | 0.90 | |||||
1000 | 1860 | 9220 | 9780 | 10400 | 0.80 | |||||
1250 | 2140 | 10800 | 11500 | 12300 | 0.80 | |||||
1600 | 2510 | 13,000 | 13800 | 14800 | 0.80 | |||||
2000 | 2910 | 15400 | 16300 | 17500 | 0.60 | |||||
2500 | 2480 | 18200 | 19300 | 20700 | 0.60 | |||||
2000 | 2910 | 16800 | 17800 | 19100 | 0.60 | 8 | ||||
2500 | 3480 | 20000 | 21200 | 22700 | 0.60 | |||||
Note: The above data is only for reference when designing and selecting, and the final data is subject to the real thing. |
20kV, SC(B)12 dry-type transformer | |||||||||
Rated Capacity | High voltage | High-voltage tap range | Low Voltage | Linkage group labeling | No-load loss | Load Loss | Short Circuit Impedance | ||
B | F | H | |||||||
50 | 20 | ±2.5 | 0.4 | Dyn11 | 275 | 1230 | 1310 | 1.80 | 6.0 |
100 | 440 | 1990 | 2130 | 1.60 | |||||
160 | 540 | 2470 | 2640 | 1.40 | |||||
200 | ±2×2.5 | 590 | 2940 | 3140 | 1.40 | ||||
250 | 680 | 3420 | 3660 | 1.12 | |||||
315 | 785 | 4080 | 4360 | 1.20 | |||||
400 | 930 | 4840 | 5180 | 1.00 | |||||
500 | 1090 | 5790 | 6190 | 1.00 | |||||
630 | 1235 | 6840 | 7320 | 0.90 | |||||
800 | 1415 | 8260 | 8440 | 0.90 | |||||
1000 | 1675 | 9780 | 10400 | 0.80 | |||||
1250 | 1930 | 11500 | 12300 | 0.80 | |||||
1600 | 2260 | 13800 | 14800 | 0.80 | |||||
2000 | 2620 | 16300 | 17500 | 0.60 | |||||
2500 | 3130 | 19300 | 20700 | 0.60 | |||||
2000 | 2620 | 17800 | 19100 | 0.60 | 8.0 | ||||
2500 | 3130 | 21200 | 22700 | 0.60 | |||||
Note: The above data is only for reference when designing and selecting, and the final data is subject to the real thing. |
Recommend Products
Consult
We will offer custom quotes and powerful solutions to meet your needs. Send us your details and we'll get back to you as soon as possible.