Model: KYN28A-12- /□□ Rated voltage: 3.6,7.2,12 Rated frequency: 50Hz

Key Words:

KYN28A-12 armored move-open type AC metal-enclosed switchgear

Product Details Product parameters

Product Model Meaning

Model number

K

Y

N

28A

-

12

Number

meaning

Metal-enclosed armored

Removable (trolley center)

For indoor use

Design number

 

Rated Voltage
(kV)

Primary circuit scheme

Environmental Characteristics Designator:

TH - for humid tropics;

TA - for dry tropics;

G - for high altitude;

C - for cold tropics

Product Overview

KYN28A-12 type of indoor AC armored move-open metal-enclosed switchgear. It is suitable for three-phase AC rated voltage 12KV, rated frequency 50Hz power system, used for receiving and distributing electric energy and circuit control, protection and monitoring. This product is in line with GB3906 "3 ~ 35KV AC metal-enclosed switchgear", GB/T11022 "high-voltage switchgear and control equipment standard common technical requirements", EC60298 "rated voltage 1kV above 52KV and below AC metal enclosure switchgear and control equipment", DL/T404 "indoor AC high-voltage switchgear ornamental technical conditions" standard requirements. Requirements.

Conditions Of Use

1. Ambient temperature: Maximum temperature +40℃, minimum temperature -15℃ (under special process, up to -45℃).

2. Environmental humidity: Daily average <95%. Monthly average ≤90%.

3. Altitude: Below 1000m;

4. Seismic resistance: Seismic intensity not exceeding 8;

5. The surrounding air should be free of corrosive or combustible gases, water vapor and other obvious pollution;

6. No serious filth and frequent violent vibration, severe conditions under severe degree of design to meet the requirements of category 1;

7. When used under normal environmental conditions exceeding those specified in GB3906, it is negotiated between the user and the manufacturer.

Note:

 ①The electric heater should be connected when the relative humidity is more than 70%. 

② Where the altitude exceeds 1000m, according to JB/Z102-71 regulations.

Technical Parameters
sports event unit (of measure) parameters
rated voltage kV 3.6, 7.2, 12
Rated frequency Hz 50
Circuit Breaker Rated Current A 630, 1250, 1600, 2000, 2500, 3150
Switchgear rated current A 630, 1250, 1600, 2000, 2500, 3150
Rated dynamic stabilizing current kA 16, 20, 25, 31.5, 40, 50
Rated stabilizing current (peak) kA 40, 50, 63, 80, 100, 125
Rated short-circuit breaking current kA 16, 20, 25, 31.5, 40, 50
Rated short-circuit closing current (peak) kA 40, 50, 63, 80, 100, 125
Rated insulation level 1min frequency withstand voltage kV 24 32 42
Lightning Surge Withstand Voltage 40 60 75
protection class   IP4X for the enclosure, IP2X for the isolation compartment, breaker compartment with the door open
VD4, VS1-12 vacuum circuit breaker technical parameters
sports event Unit Parameter
rated voltage kV 12
Rated frequency Hz 50
Circuit Breaker Rated Current A 630, 1250, 1600, 2000, 2500, 3150
Rated dynamic stabilizing current (4S) kA 16, 20, 25, 31.5, 40, 50
Rated stabilizing current (peak) kA 40, 50, 63, 80, 100, 125
Rated short-circuit breaking current kA 16, 20, 25.31.5, 40, 50
Rated short-circuit closing current (peak) kA 40, 50, 63, 80, 100, 125
Rated insulation level 1min frequency withstand voltage kV 42
Lightning Surge Withstand Voltage kV 75
Rated sequence of operation   min-0.3s-combined min-180s-combined min 50
Rated short-circuit breaking current breaking times substandard 50
mechanical life substandard 20000
VD4, VS1 Vacuum Circuit Breaker Mechanical Characteristics
sports event unit (of measure) parameters
contact opening distance mm 11±1
overtravel mm 4±0.5
Interphase center distance mm 210±0.5,275±0.5
Closing contact bounce time ms ≤2
Three-phase switching non-simultaneity ms ≤2
Opening time when the operating voltage is supreme ms ≤50
rated ms ≤50
lowest ms ≤60
Closing time ms ≤100
Average closing speed m/s 0.9-1.2
Average gate opening speed m/s 0.6-0.8
When the circuit breaker is used to control 3-10kv motor, if the starting current is less than 600A, metal zinc oxide surge arrester must be added, and the specific requirements are negotiated between the user and our company: when the circuit breaker is used to disconnect the capacitor bank, the rated current of the capacitor should not be greater than 80% of the rated current of the circuit breaker.
Technical parameters of the operating mechanism
sports event unit (of measure) parameters
Rated operating voltage Closing coil V AC/DC220,110
Split gate coil V AC/DC220,110
Coil power Closing coil W 245
Split gate coil W 245
Energy storage motor power W 50
Rated voltage of energy storage motor V AC/DC220,110
Energy storage time S ≤10

Note: The above data is only for reference when designing and selecting, and the final data is subject to the real thing.